Abstract : A current transformer transient model was implemented, usingElectromagnetic Transient Program (EMTP), nonlinear inductor (Type-96) inorder to investigate the effects of CT's saturation on digital overcurrentrelays. The model was validated by testing in laboratory and found to beeffective, reliable and accurate for evaluations of digital overcurrent relays,during CT's saturation. Factors that lead to CT's saturations werecomprehensively discussed and evaluated.A typical digital overcurrent relay was tested in the laboratory toinvestigate the effects of secondary.